| ==Goals==; *Install a network of Ethernet-capable vacuum gauges to replace the old serial-switchbox units. *Replace the EPICS/hardware translation layer with Python-based code. *Other hardware changes? Valves, pumps, computers? |
== Goals == |
| Line 8: | Line 5: |
| ==List of Hardware That Will Interface with New Digital System==; ||'''Component'''||||'''Location'''||||'''Link to product info'''|| ||e.g., Ethernet gauge||||x-end||||https://products.inficon.com/en-us/nav-products/product/detail/vgc50x/|| |
|| The primary purpose of this vent is to simply replace the VME system with an Acromag system and verify that we are at the same operating state as we are at now (so the pump and gauge hardware is NOT upgraded for now). This amounts to implementing Python logic for the [[https://wiki-40m.ligo.caltech.edu/Vacuum_Interlocks?highlight=%28interlocks%29|INTERLOCKS]] and checking that they work. The zeroth level test can be done o the electronics bench, by just changing EPICS values for pressure indicators and seeing that the appropriate DAC/BIO channels are triggered. https://wiki-40m.ligo.caltech.edu/Vacuum_Interlocks?highlight=%28interlocks%29|| |
| Line 12: | Line 7: |
| Diagram of where pumps, valves, gauges are located in the system? | == Design Documents == |
| Line 14: | Line 9: |
| ==References==; *[[http://www.ligo.caltech.edu/~ajw/40m/40mProcedures.doc|Documentation on current software design]] *[[https://dcc.ligo.org/DocDB/0015/D000338/000/D000338-00.pdf|Wiring diagrams]] |
Schematics of current and proposed signal flows. Includes a parts list for new hardware. [[attachment:40m_Vacuum_System_Signal_Flow.pdf]] List of all vacuum EPICS channels. [[attachment:slow_channel_list.pdf]] Physical channel assignments to the Acromag cards. [[attachment:AcromagChannelAssignment.pdf]] == Options for later hardware upgrades == *good web site of gauges + : https://confluence.slac.stanford.edu/pages/viewpage.action?pageId=178520731#Gauges/Controllers-ColdCathode ||'''Component'''||||'''Notes'''||||'''New/Replacement/Carryover'''||||'''Link to product info'''|| ||e.g., Ethernet gauge||||x-end||||replacement||||https://products.inficon.com/en-us/nav-products/product/detail/vgc50x/|| ||EthernetIP Gateway||||pumpspool||||option||||https://www.frederickscompany.com/wp-content/uploads/2018/06/mx_ag_eip_ds.pdf/|| ||Ethernet-Serialport Adapter||||2 purchased||||for gauge test Acromag||||https://reviewfinch.com/p/ONETAK-TCP-IP-Ethernet-RJ45-to-Serial-RS232-RS485-RS422-Converter-Adapter-Adaptor/170160/|| ||cold cathode gauges||||need 7||||no serial port||||http://www.instrutechinc.com/cold-cathode-vacuum-gauge-hornet/|| ||cold cathode ||||option||||gauge with RS485||||https://thyracont-vacuum.com/products/smartline-vacuum-transducers/vsi-vacuum-transducer-cold-cathode/vsi1xd-vacuum-transducer/|| ||cold cathode 971 & 972||||cc & or pirani||||with RS485||||https://www.mksinst.com/docs/ur/970selector.aspx/|| || 972 & 925 |||| ccp & pirani |||| ethernetCAT_??? |||| https://www.mksinst.com/docs/UR/970-DS.pdf|| *http://www.galilmc.com/news/white-paper-ethernet-or-ethercat-motion-control-choosing-right-network-your-application [[attachment:MKS_Gauges_Quote.pdf]] * 10-30-2018SV I learned it today that Serial Port to Ethernet Conversion is not reliable so scrap this MKS quote. I did not find any gauges with Ethernet output. Now we have a clear direction. Reality today that gauges come with serial ports. The sites just upgraded to gauge BPG400 with serial ports. *existing Cold Cathode gauges 423 & or 421 [[https://www.mksinst.com/docs/UR/943DS.pdf]] *existing Pirani gauges are 275 Convectron [[https://www.mksinst.com/product/product.aspx?ProductID=1426]] *valve actuator relay [[attachment:24V relay-Valve.pdf]] == References == *[[http://www.ligo.caltech.edu/~ajw/40m/40mProcedures.doc|Old software design]] *[[https://dcc.ligo.org/DocDB/0015/D000338/000/D000338-00.pdf|Old wiring diagrams]] *[[https://wiki-40m.ligo.caltech.edu/Vacuum-Upgrade-2018?action=AttachFile&do=view&target=old_40m_procedures.pdf|Old vacuum procedures manual]] |
Fall 2018 Upgrade of 40m Vacuum System
Goals
The primary purpose of this vent is to simply replace the VME system with an Acromag system and verify that we are at the same operating state as we are at now (so the pump and gauge hardware is NOT upgraded for now). This amounts to implementing Python logic for the INTERLOCKS and checking that they work. The zeroth level test can be done o the electronics bench, by just changing EPICS values for pressure indicators and seeing that the appropriate DAC/BIO channels are triggered. https://wiki-40m.ligo.caltech.edu/Vacuum_Interlocks?highlight=%28interlocks%29 |
Design Documents
Schematics of current and proposed signal flows. Includes a parts list for new hardware. 40m_Vacuum_System_Signal_Flow.pdf
List of all vacuum EPICS channels. slow_channel_list.pdf
Physical channel assignments to the Acromag cards. AcromagChannelAssignment.pdf
Options for later hardware upgrades
good web site of gauges + : https://confluence.slac.stanford.edu/pages/viewpage.action?pageId=178520731#Gauges/Controllers-ColdCathode
Component |
Notes |
New/Replacement/Carryover |
Link to product info |
|||
e.g., Ethernet gauge |
x-end |
replacement |
https://products.inficon.com/en-us/nav-products/product/detail/vgc50x/ |
|||
EthernetIP Gateway |
pumpspool |
option |
https://www.frederickscompany.com/wp-content/uploads/2018/06/mx_ag_eip_ds.pdf/ |
|||
Ethernet-Serialport Adapter |
2 purchased |
for gauge test Acromag |
||||
cold cathode gauges |
need 7 |
no serial port |
http://www.instrutechinc.com/cold-cathode-vacuum-gauge-hornet/ |
|||
cold cathode |
option |
gauge with RS485 |
||||
cold cathode 971 & 972 |
cc & or pirani |
with RS485 |
||||
972 & 925 |
ccp & pirani |
ethernetCAT_??? |
||||
- 10-30-2018SV I learned it today that Serial Port to Ethernet Conversion is not reliable so scrap this MKS quote. I did not find any gauges with Ethernet output. Now we have a clear direction. Reality today that gauges come with serial ports. The sites just upgraded to gauge BPG400 with serial ports.
existing Cold Cathode gauges 423 & or 421 https://www.mksinst.com/docs/UR/943DS.pdf
existing Pirani gauges are 275 Convectron https://www.mksinst.com/product/product.aspx?ProductID=1426
valve actuator relay 24V relay-Valve.pdf